Function
Packages built to promote heat recovery from flash steam, condensate or both. Especially recommended for heating a continuous flow of fluid, such as make-up water to a boiler feedwater system.
-
Use
Steam, water, hot condensate and other fluids compatible with the construction.
-
Maximum allowable (primary) pressure
up to 13 bar for saturated steam
-
Maximum allowable (primary) temperature
for saturated steam: 250 ºC
-
Сondensate heating
above 100 ºC
-
Steam boiler(s) perating pressure(s) and temperature
boilers up to 20 bar – 220 ºC
-
Trap discharge capacity
Max.: up to 50000 kg/h
-
Differential pressure on trap
Delta P: 4,5 , 10 and 12 bar
-
Pipework pressure rating
PN 16
-
Non-standard design
Atmospherically vented units, to avoid extra back pressure in the condensate return system,
Different types of materials and designs available, according to the application. -
Connections
Flanged EN 1092-1 PN 16,
Flanged ASME B16.5 Class 150 on request